    Sliding Fire Doors

     

Sliding Fire Doors


Sliding Fire doorsets consist of door leaf, associated track and counterweights with steel facings, available in 2 hours and 4 hours of certified fire resistance.

Ideal for applications that require a certified sliding fire door especially in hospitals, schools, public buildings, shopping centres, factories, warehouses, etc.

Fusible Link System: Door is opened and closed manually in case of fire door closes automatically from any given position

Pyropanel Electric System (BCA Kit):  Door is opened manually and will be held open by an electromagnet when the building is in use. Door is released to close using a release switch. In case of fire the door is released (closed) by a smoke/heat detector.

Sliding Fire Doors

Product Range


FRL

Thickness

Max Leaf Size - Single

Max Leaf Size - Pair

Download Tech Sheet

-/120/120

80mm

5000(h) x 6000(w)#

5000(h) x 6000(w)#

Download Product Tech Sheet - Opens in a new window Download

-/240/120

80mm

5000(h) x 6000(w)#

5000(h) x 6000(w)#

Download Product Tech Sheet - Opens in a new window Download

Notes:
  • All sliding fire doors must overlap top and both sides of opening by 75mm.
  • Wall surfaces along the travel should be level with a maximum recommended tolerance of 5mm.
  • Maximum clearance between door and floor should be 10mm.
  • Ensure no wall obstruction along the distance of travel.
  • Allow 250mm clear wall area for counter-weight case.
Features
  • Protection of openings in up to 4hr Concrete/Masonry walls.
  • Facing – 1.0mm zincanneal sheet steel as standard, alternative of 4mm decorative fire retardant chemical treated plywood available.
  • All doors have steel channels to protect edge of door leaves
  • Can be manufactured in sections and assembled on site for easier transport and handling.